MG series wood pellet boilers (with burners)

Designed to heat industrial, commercial or public premises using wood pellets. Especially suitable in situations when there is a demand for the efficient and environmentally friendly heating equipment. 

Benefits:

  • ECONOMICAL: saves money
    Efficient use of fuel because the intelligent boiler control system ensures that the pellets are fed into the burner evenly and only as much as necessary to maintain the target temperature. 
  • EASY MAINTENANCE: saves time on maintenance and service
    These processes controlled automatically: heat exchanger cleaning, ash removing, ignition and extinguishing. Intelligent control system ensures monitoring of the boiler operating parameters via internet. Therefore, no additional staff is required to maintain the boiler. 
  • ENVIRONMENTAL FRIENDLY
    Low CO2 emissions. Low concentration of dust avoids investment in additional filtering system and a multicyclone.
  • MODERN DESIGN AND MANAGEMENT
    The boiler is compact, quick to set up and easy to provide heat for a variety of applications. Fuel burning process is controlled by a programmable digital controller and a sensor system that tracks and controls the combustion process of the boiler: from the amount of oxygen in the smoke to the fuel supply to the burner; fan speed; automatically switches the system pumps on or off depending on the boiler temperature. This ensures efficiency, optimum combustion conditions, reduces fuel consumption and minimalize environmental pollution.

BOILER CONTROLLER CONTROLS:

  • Exhauster
  • Ash removal gears
  • Heat exchanger cleaning

 CONTROLLER MONITOR AND MANAGE:

  • Boiler emergency overheating (with emergency thermostat)
  • Boiler pressure (too high or too low)
  • Interruption of heat transfer through the boiler
  • Overloads of boiler gears
  • Constant draught in the boiler furnace by managing the exhaust gas fan operating mode with frequency converter and differential pressure sensor

 

BURNER CONTROLLER CONTROLS:

  • Burner gears operation  
  • Automatic performance adjustment
  • Recirculation pump (according to active mode)
  • Automatic start and stop of the burner
  • The amount of oxygen in the smoke
  • Burner flame control
  • Burner faults diagnostics
  • Adjustment of fuel supply. Modular increase / decrease of fuel supply in proportion to the thermal load 

 BOILER MONITORING:

  • Real-time and remote monitoring of burner operating parameters, as well as data and emergency message storage and ability to view stored data (with Internet access)
  • Burner thermal power
  • Water supply from boiler
  • Return water temperature
  • Outside temperature
  • Fuel channel temperature

Boiler model

Kalvis-100MG

Kalvis-150MG

Kalvis-200MG

Kalvis-250MG

Kalvis-300MG

Kalvis-400MG

Kalvis-500MG

Nominal power (QN)  kW

100

150

200

250

300

400

500

Minimal power (Qmin) kW

30

45

60

75

90

120

150

Fuel used

wood pellets

Fuel humidity, not more than  (%)

10

Fuel dimensions, not more than (mm)

6 – 8

Fuel consumption at nominal output ( kg/h)

20

37

52

65

77

114

150

Efficiency at QN, not less than ( %)

90

Heating premises, m2

B class

1170..3500

1755..5250

2340..7000

2925..8750

3510..10500

4680..14000

5850…17500

C class

560..1670

840..2505

1120..3340

1400..4175

1680..5010

2240..6680

2800…8350

Burning time without refueling (at QN)

depends on fuel bunker

Boiler class acc to  LST EN 303-5

5

Lifetime in years, not less than

10

Water volume in the boiler (l)

990

990

1200

1200

1400

1400

1600

Water pressure in the boiler,

 bar (MPa)

not less than

2,5 (0,25)

not more than

Maximum permitted operating water temperature  (ºC)

90

Minimum return water temperature during operation (ºC)

50

Hydraulic resistance (Δt=20ºC/Δt=10ºC) (mbar)

0,014

0,035

0,07

0,127

0,136

0,185

0,254

Ambient temperature (ºC)

3-30

Draught from the boiler (Pa)

180

Flue gas temperature at nominal output, up to (ºC)

130

Electrical voltage (V)

230 AC

Electrical power (W)

455

585

585

585

1111

1411

1466

Electrical protection degree

IP 20

Dimensions of connection flanges: (mm)

flue channel (conditional vlue) mm

Ø 200

Ø 250

flue channel flange, mm

Ø 255

Ø 305

drain, mm

25 (1″)

heating system, mm

50 (2″)

65 (2½”)

Mass, not more than (±10%)

kg

2200

2300

2500

2750

3000

3550

 

UAB KALVIS reserves the right to make changes of parameters and sizes of equipment during product development process.

Boiler model

 

Kalvis-100MG

Kalvis-150MG

Kalvis-200MG

Kalvis-250MG

Kalvis-300MG

Kalvis-400MG

Kalvis-500MG

Overall dimensions,

height (H)

mm

1920

2020

2020

2180

2180

2220

2220

not more than:

 

 

 

width, with control panel (B)

mm

1440

1440

1440

1560

1560

1720

1720

width, without control panel (B1)

mm

1140

1140

1140

1260

1260

1420

1420

length without burner (L1)

mm

3000

3100

3100

3100

3100

3450

3650

dimension in front for service (L2)

mm

1700

2000

2000

2000

2000

2300

2500

 

 